background image

   

Industrial

 

Electronic Devices 

 

 

 ADFweb.com S.r.l. 

 

User Manual   

BACnet Slave / Modbus Master

 

 

Document code: MN67671_ENG     Revision 1.100   Page 1 of 34

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 

 

User Manual 

Revision 1.100 
English 

 

BACnet/IP Slave / Modbus Master - 
Converter 

 (Order Code:  HD67671-IP-2-A1, HD67671-IP-4-A1) 

BACnet MS/TP Slave / Modbus Master - 
Converter 

 (Order Code:  HD67671-MSTP-2-A1, HD67671-MSTP-4-A1) 

 

For Website information:  

www.adfweb.com?Product=HD67671

 

 

For Price information: 

www.adfweb.com?Price=HD67671-IP-2-A1

 

www.adfweb.com?Price=HD67671-IP-4-A1

 

www.adfweb.com?Price=HD67671-MSTP-2-A1

 

www.adfweb.com?Price=HD67671-MSTP-4-A1

 

 

Benefits and Main Features: 

 

Triple electrical isolation 

 

Two BACnet ports 

 

Temperature range: -40°C/85°C (-40°F/185°F) 

 

For others BACnet products see also the following link: 

 

Converter BACnet slave to  

www.adfweb.com?Product=HD67056

      

(M-Bus Master) 

www.adfweb.com?Product=HD67086

      

(M-Bus Wireless) 

www.adfweb.com?Product=HD67170

      

(SNMP Manager)

 

www.adfweb.com?Product=HD67670

      

(DMX)

 

www.adfweb.com?Product=HD67671

      

(Modbus Master)

 

www.adfweb.com?Product=HD67672

      

(Modbus Slave) 

www.adfweb.com?Product=HD67673

      

(Modbus TCP Master)

 

www.adfweb.com?Product=HD67674

      

(Modbus TCP Slave)

 

www.adfweb.com?Product=HD67675

      

(PROFIBUS Master)

 

www.adfweb.com?Product=HD67676

      

(PROFIBUS Slave)

 

www.adfweb.com?Product=HD67677

      

(CAN)

 

www.adfweb.com?Product=HD67678

      

(CANopen)

 

www.adfweb.com?Product=HD67679

      

(PROFINET)

 

www.adfweb.com?Product=HD67680

      

(DeviceNet Master) 

www.adfweb.com?Product=HD67681

      

(DeviceNet Slave) 

www.adfweb.com?Product=HD67682

      

(EtherNet/IP) 

www.adfweb.com?Product=HD67683

      

(NMEA 2000) 

www.adfweb.com?Product=HD67684

      

(Ethernet) 

www.adfweb.com?Product=HD67685

      

(J1939) 

www.adfweb.com?Product=HD67693

      

(SNMP Agent)

 

www.adfweb.com?Product=HD67802

      

(KNX)

 

www.adfweb.com?Product=HD67833

      

(DALI)

 

 

 

Do you have an your customer protocol? 

www.adfweb.com?Product=HD67003

 

 

Do you need to choose a device? do you want help? 

www.adfweb.com?Cmd=helpme

 

 

User Manual   

 

Axis Solutions Pvt Ltd is the Authorized Distributor of 

$')ZHE

 in India  

www.axisindia.in | [email protected]

Axis Solutions Pvt Ltd is the Authorized Distributor of 

$')ZHE

 in India  

www.axisindia.in | [email protected]

Axis Solutions Pvt Ltd is the Authorized Distributor of 

$')ZHE

 in India  

www.axisindia.in | [email protected]

Axis Solutions Pvt Ltd is the Authorized Distributor of 

$')ZHE

 in India  

www.axisindia.in | [email protected]

Summary of Contents for AXIS HD67671-IP-2-A1

Page 1: ...eb com Product HD67673 Modbus TCP Master www adfweb com Product HD67674 Modbus TCP Slave www adfweb com Product HD67675 PROFIBUS Master www adfweb com Product HD67676 PROFIBUS Slave www adfweb com Pro...

Page 2: ...TATION Dear customer we thank you for your attention and we remind you that you need to check that the following document is Updated Related to the product you own To obtain the most recently updated...

Page 3: ...device can be used only by qualified personnel strictly in accordance with the specifications Qualified personnel are persons who are familiar with the installation assembly commissioning and operati...

Page 4: ...Industrial Electronic Devices ADFweb com S r l User Manual BACnet Slave Modbus Master Document code MN67671_ENG Revision 1 100 Page 4 of 34 EXAMPLE OF CONNECTION...

Page 5: ...Industrial Electronic Devices ADFweb com S r l User Manual BACnet Slave Modbus Master Document code MN67671_ENG Revision 1 100 Page 5 of 34...

Page 6: ...ustrial Electronic Devices ADFweb com S r l User Manual BACnet Slave Modbus Master Document code MN67671_ENG Revision 1 100 Page 6 of 34 CONNECTION SCHEME Figure 1a Connection scheme for HD67671 IP 2...

Page 7: ...Industrial Electronic Devices ADFweb com S r l User Manual BACnet Slave Modbus Master Document code MN67671_ENG Revision 1 100 Page 7 of 34 Figure 1b Connection scheme for HD67671 IP 4 A1...

Page 8: ...Industrial Electronic Devices ADFweb com S r l User Manual BACnet Slave Modbus Master Document code MN67671_ENG Revision 1 100 Page 8 of 34 Figure 1c Connection scheme for HD67671 MSTP 2 A1...

Page 9: ...Industrial Electronic Devices ADFweb com S r l User Manual BACnet Slave Modbus Master Document code MN67671_ENG Revision 1 100 Page 9 of 34 Figure 1d Connection scheme for HD67671 MSTP 4 A1...

Page 10: ...Cnet Power Supply BACnet Modbus Power Supply Modbus Two directional information between BACnet bus and Modbus bus Mountable on 35mm Rail DIN Wide power supply input range 8 24V AC or 12 35V DC Wide te...

Page 11: ...WER SUPPLY The devices can be powered at 8 24V AC and 12 35V DC For more details see the two tables below VAC VDC Vmin Vmax Vmin Vmax 8V 24V 12V 35V Consumption at 24V DC Device Consumption W VA HD676...

Page 12: ...t with Dip2 of Dip Switch A at OFF position is used for the normal working of the device The second with Dip2 of Dip Switch A at ON position is used for uploading the Project and or Firmware For the o...

Page 13: ...powered OFF Device not powered 2 Modbus comm green Change state when Modbus replies arrive Blinks quickly Boot state Blinks very slowly 0 5Hz update in progress 3 Device state green Blinks slowly 1Hz...

Page 14: ...Normal Mode Boot Mode 1 Device State Blinks slowly 1Hz Blinks quickly Boot state Blinks very slowly 0 5Hz update in progress 2 Link Ethernet ON Ethernet cable connected OFF Ethernet cable disconnected...

Page 15: ...dip 1 like in figure The maximum length of the cable should be 1200m 4000 feet Here some codes of cables Belden p n 8132 2x 28AWG stranded twisted pairs conductor foil shield braid shield Belden p n...

Page 16: ..._ENG Revision 1 100 Page 16 of 34 RS232 The connection from RS232 socket to a serial port example one from a personal computer must be made with a NULL MODEM cable a serial cable where the pins 2 and...

Page 17: ...connections in cat 5 up to 100 Mbps To connect the device to an Hub Switch is recommended the use of a straight cable to connect the device to a PC PLC other is recommended the use of a cross cable HD...

Page 18: ...runs with Windows called SW67671 It is downloadable from the site www adfweb com and its operation is described in this document this manual is referenced to the last version of the software present...

Page 19: ...iguration A device s configuration can also be imported or exported To clone the configurations of a Programmable BACnet slave Modbus master Converter in order to configure another device in the same...

Page 20: ...e the language of the software and check the updatings for the compositor In the section Language it is possible to change the language of the software In the section Connection Options it is possible...

Page 21: ...et Slave Modbus Master Document code MN67671_ENG Revision 1 100 Page 21 of 34 In the section Software Settings it is possible to enable disable some keyboard s commands for an easier navigation inside...

Page 22: ...of the converter is defined In the fields SUBNET Mask the SubNet Mask of BACnet IP side of the converter is defined In the fields GATEWAY the default gateway of the network is defined This feature ca...

Page 23: ...used for the Modbus communication is defined In the field Baudrate the data rate of the Modbus line is defined In the field Parity the parity of the Modbus line is defined In the field Stop Bits the n...

Page 24: ...Frames specifies the maximum number of information frames the node may send before it must pass the token In the field Device Instance the of the BACnet MS TP side of the converter is defined In the...

Page 25: ...Manual BACnet Slave Modbus Master Document code MN67671_ENG Revision 1 100 Page 25 of 34 SET MODBUS ACCESS By Pressing the Set Modbus Access button from the main window for SW67671 Fig 2 the window S...

Page 26: ...ber of consecutive errors that the Master waits before discarding the row from the cycle of requests is defined In the field Position the position byte where taking saving the data from to the interna...

Page 27: ...BACnet Master the Modbus registers associated to these objects are written by Modbus Master The meaning of the fields in the window are the follows In the field Data Type it is possible to select the...

Page 28: ...ted BACnet Engineering Unit field or by selecting with the fields Select the Type and Select unit the Type Unit desired If the second way is used is necessary to press the Select Engineering Unit butt...

Page 29: ...r Press the Next button Select which operations you want to do Press the Execute update firmware button to start the upload When all the operations are OK turn OFF the Device Put Dip2 of Dip Switch A...

Page 30: ...to restart the PC Check the LAN settings Check the Wi Fi settings If you are using the program inside a Virtual Machine try to use in the main Operating System If you are using Windows Seven Vista 8...

Page 31: ...N67671_ENG Revision 1 100 Page 31 of 34 MECHANICAL DIMENSIONS Figure 9a Mechanical dimensions scheme for HD67671 IP 2 A1 Figure 9b Mechanical dimensions scheme for HD67671 IP 4 A1 Figure 9c Mechanical...

Page 32: ...Cnet IP MSTP BACnet MS TP Device Family HD67671 BACnet Slave Modbus Master Converter Order Code HD67671 IP 2 A1 BACnet IP slave Modbus master Converter Modbus over RS232 Order Code HD67671 IP 4 A1 BAC...

Page 33: ...ction systems This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish Instead it should be taken to an applicable collection point for the re...

Page 34: ...dress provided with the PRN having prepaid the shipping costs shipment costs billed to us will not be accepted If the product is within the warranty of twelve months it will be repaired or exchanged a...

Reviews: