LTPS-UM-8007-01, Issue 1
32
November 9, 2001
SPX-CABFIN01, SPX-CABFIN04
16
If the cabinet:
–
Is not equipped with a BTRM System, proceed to Step 19.
–
Is equipped with a BTRM System, continue with Step 17.
17
Locate the bag of eight TSUs in the loose parts kit.
18
Install a TSU on the negative terminal.
For details, refer to Lorain Products Installation Instructions.
19
Install the flat washer and lock washer, and install (but do not tighten) the terminal fastener (screw or nut).
20
Position the battery cable ends as shown in
. Tighten both battery terminals
to a torque of 65-70 in-lb (735-790 [N-cm]) maximum.
Figure 25.
Battery Cable Installation of Stud Terminal
Chloride PowerSafe batteries have a red disc below the positive (+) terminal and a blue disc
below the negative (-) terminal.
The TSUs (about 3/4 in. diameter) are labeled 428804800 60°C.
One TSU is to be installed at each battery negative post.
Positive
lead
Flat washer
TSU
Hex nut
Lock washer
Negative
terminal
Negative
lead
Anderson