![ADC Soneplex Soneplex Fiber Hub Cabinet SPX-CABFIN04 User Manual Download Page 49](http://html1.mh-extra.com/html/adc/soneplex-soneplex-fiber-hub-cabinet-spx-cabfin04/soneplex-soneplex-fiber-hub-cabinet-spx-cabfin04_user-manual_2848187049.webp)
LTPS-UM-8007-01, Issue 1
Installation
SPX-CABFIN01, SPX-CABFIN04
November 9, 2001
37
–
If the battery string voltage does not fall within the acceptable range, ensure that batteries are properly
connected.
–
If no problems are found and the battery string still falls below the acceptable limit, contact your
technical support group.
DO NOT PROCEED until the problem is corrected.
6
If the batteries:
–
are in one 6V string, proceed to Step 10.
–
are in two 12V strings, continue with Step 7.
7
If two 12V battery strings are used, reconnect all battery bus connectors for the second string (under test), and
isolate the second string:
–
At the DC distribution panel, ensure that the battery disconnect is operated (the pin provided at the
right-hand side is inserted into the BATTERY DISCONNECT jack as shown in
–
Disconnect any one connector from the battery connector bus for the first string of batteries.
8
Repeat Step 4 and Step 5 for the battery string under test.
9
Remove the pin from the BATTERY DISCONNECT jack.
10
Ensure that all battery bus connectors are reconnected.