LTPS-UM-8007-01, Issue 1
Prior to Installing the SPX-CABFIN
SPX-CABFIN01, SPX-CABFIN04
November 9, 2001
9
14
Treat the area below the pad, and for two feet around the perimeter, for insects (refer to local practices).
Figure 6.
Foundation Pad Design
P
OURING
THE
P
AD
The concrete compression strength must be a minimum of 4,000 psi, as determined by ASTM
C39, Test of Compression Strength of Concrete Cylinders. The slump of the concrete must be 2
to 4 inches, as determined by ASTM C143.
Coarse aggregate used in the concrete shall be graded from 3/4 inch to No. 4 only.