Refrigerant Charge Details (R-410A)
Model
CRV140S CRV160S
CRV180S CRV160T CRV180T
CRV210T
CRV240T
Refrigerant Type
R-410A
R-410A
R-410A
R-410A
R-410A
R-410A
R-410A
Factory Charge
gms
5580
6300
7580
6200
7850
7400
9350
Pre- charged Length
m
15
15
15
15
15
15
15
Additional Refrigerant
per charge
gms
50
50
50
50
50
50
100
100
Field Pipe Sizing
In.(mm)
LIQ. 3/8” (9.52) 3/8” (9.52) 3/8” (9.52) 3/8” (9.52) 3/8” (9.52) 3/8” (9.52)
(1)
1/2”(12.7)
1/2”(12.7)
GAS
3/4”
(19.05)
3/4”
(19.05)
3/4”
(19.05)
3/4”
(19.05)
7/8”
(22.22)
7/8” (22.22)
1” (25.4)
1” (25.4)
NOTE
(1)
50grams per meter is only applicable if 3/8” liquid field pipe is used (for field pipe length between 0-20m).