Installation and Commissioning Guide - Advance Split Ducted Outdoor Unit
Doc. No.0525-085 Ver. 2 22xxxx
Installation and Commissioning Guide
Advance Outdoor Units
54
PRELIMINARY DATA ONLY
Ver. 2.04 220704
THIS LABEL TO BE REMOVED ON SIGN-OFF
EVV240S / EFV240S
APPLICATION RANGE (COMPRESSOR ON) *
AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
50
100
150
200
250
300
350
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
900
40
292
44
359
48
440
52
515
59
596
78
684
98
739
950
43
321
47
394
52
491
56
567
66
650
84
741
1000
47
365
51
441
55
522
59
606
73
707
93
794
1050
51
410
55
490
59
575
64
669
79
765
99
828
1100
55
456
59
541
63
629
69
726
87
826
1130
57
485
62
579
66
673.2
73
767.6
92
861.4
1150
59
504
63
592
68
703
76
795
96
885
1200
63
554
68
663
73
771
84
868
1250
68
622
73
736
78
834
93
924
1300
73
692
78
810
84
912
1350
78
762
83
882
92
970
1360
79
777
84
894
94
989
NOTES
* Only applicable to Third Party controllers
W = Indoor Fan Power, Watts
PWM = Pulse Width Modulation Setting, % PWM (Adjustable through the LR7-1, LC7-2, NEO or Outdoor Board).
Default Fan Speed Value at 100 Pa
Speed
Default PWM (adjustable)
Indoor Fan PWM Limits
High PWM (%)
84
High PWM Limit
99
Medium PWM (%)
62
Low PWM Limit
39
Low PWM (%)
44
MOTOR / BLOWER UNIT