Installation and Commissioning Guide - Advance Split Ducted Outdoor Unit
Doc. No.0525-085 Ver. 2 22xxxx
Installation and Commissioning Guide
Advance Outdoor Units
38
PRELIMINARY DATA ONLY
Ver. 2.04 220704
THIS LABEL TO BE REMOVED ON SIGN-OFF
Third Party Control Input (Indoor and/or Outdoor Board)
This option allows Fan, Compressor and Reversing Valve to be controlled by a Third Party Control. There are two ways
on how the Indoor Fan may be controlled, using 0-10V Analogue Input or Fixed Indoor Fan Speed.
NOTE
• Demand Response Management (DRM) is not available if Third Party Control Option is used.
• Make ensure control source has been configured for Third Party Control.
0-10V Analogue Input for Compressor and Indoor Fan
Indoor Fan Connection (Indoor Board)
THIRD PARTY
INDOOR FAN
CONTROL
INPUT
COM
0-10VDC
ID FAN INPUT
0-
10V C
OM
A
UX IN
Input (DC)
Output
Fan Status
0.0V to 0.99 V
0%
Off
1.0V to 1.49 V
0 or 20%
Off or On
1.5V to 9.5 V
20% to 100%
On
9.5V to 10 V
100%
On
Compressor and Reversing Valve Connection (Outdoor Board)
FAN IN
WALL CONTROLLER
OUTDOOR
ECON OUT
AUX OUT
AUX IN
+12
V
0-
10
V
+12V
CO
M
CO
M
A
A
0-
10
V
0-
10
V
B
B
CO
M
CO
M
G
G
PWM FAN OUTPUT
0-10V FAN INPUTS
INTERNAL FAN SPEED
OFF
ON
1 2 3 4 5 6 7 8
INDOOR CONTROL BOARD
0-10V INDOOR FAN
DIP SWITCH SETTING
MANUAL FAN SPEED
POT ADJUST
SMPS 240VAC/12VDC
240V AC
AMB
SENSOR
OUTPUT
0-10V G
REMOTE
ON/OFF
G 12V
+12V
COM
DRM3
COMP
DRM2
FAN
DRM1
HEAT
COIL
TEMP
LQD
HEAT
LQD
COOL
DLT
TEMP
SCT
TEMP
INDOOR 485
A B G VSD 485
A B G
AUX 485
12V A B G
OCB
FUSE
250V AC 10 A
SLOW BLOW
SIZE 5 x 20mm
B
MA
POW
AC/L
AC/N
V-
V+
COM 1
COM 2
COM 3
PWR
PROG
EXV
0-10V
INPUT
G
OFF
ON
1 2 3 4 5 6 7 8
STANDARD DIP
SWITCH SETTINGS
0-10V INPUT
0-10V INPUT
COM
COM
3RD PARTY
INDOOR FAN
CONTROL INPUT
3RD PARTY
COMPRESSOR
CONTROL INPUT
+12VDC
THIRD PARTY
COMPRESSOR
CONTROL INPUT
+12VDC
0-10V
OUTPUT
0-10V
INPUT
COM
COM
CMI
PO
T
ADJ
US
T
AM
B
SENSOR
FILT
ER
INDICA
TION
PWM
FA
N1 OUT
PWM
FA
N2 OUT
FA
N IN
WA
LL CONTROLLER
O
UT
DO
OR
485
FA
N
AUX SENSOR
EC
O
N OU
T
AUX OUT
AUX IN
+12V
0-10V
+12V
COM
COM
A
A
A
S1
0-10V
0-10V
B
B
B
COM
COM
COM
G
G
G
S2
CO
IL
TEMP
DIS
PL
AY
PWR
0-10V
0-10V
0-10V
FA
N2
O
UT
0-10V
FA
N1
O
UT
COM
COM
NC
NO
COM
COM 1
COM 2
COM 3
+12VDC
PO
WER I
N
V+
V-
ZONE
M
ASTER
SECO
NDA
RY
OFF
O
N
PW
M
F
AN
OU
TPU
T
0-10
V F
AN
INPUTS
IN
TE
RN
AL
F
AN
S
PE
ED
1
2
34
5
67
8
ST
ANDA
RD
DIP
SWITCH
SETTING
S
M
ANUA
L F
AN
SP
EED
POT
A
D
JU
ST
OPTIONA
L
OUTSIDE A
IR
DA
MPER CONTROL
OUTPU
T
OPTIONA
L
3RD PA
RTY
FA
N CONTROL
INPUT
HEAT
0-10V
G
COM
0-10VDC
INPUT
Input (DC)
Output
Compressor Status
0 - 0.99 V
0%
Off
1 - 1.49 V
0 or 20%
Off/On (hysteresis)
1.5 - 9.5 V
20% to 100%
On
9.5 - 10 V
100%
On
NOTES
• As the compressor turns ON and the Indoor fan signal is not available then indoor fan will start to run on medium
PWM speed.
• Indoor fan low and high PWM limits depends upon the model.
• The Voltage can be linearly interpolated using the above table to determine the desired PWM or unit output.