EVV160S / EFV160S
NOTES
* Only applicable to Third Party controllers
W = Indoor Fan Power, Watts
PWM = Pulse Width Modulation Setting, % PWM (Adjustable through the LR7-1, LC7-2, NEO or Outdoor Board).
APPLICATION RANGE (COMPRESSOR ON) *
AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
50
100
150
200
250
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
600
36
147
42
203
47
257
52
315
57
378
650
41
173
46
225
52
291
58
362
63
423
700
45
192
52
266
58
334
63
400
70
471
750
51
228
58
304
63
372
69
446
800
57
262
63
340
69
419
80
505
850
63
305
69
386
78
482
900
69
348
77
442
91
538
Default Fan Speed Value at 100 Pa
Speed
Default PWM (adjustable)
Indoor Fan PWM Limits
High PWM (%)
77
High PWM Limit
99
Medium PWM (%)
58
Low PWM Limit
36
Low PWM (%)
42