Installation and Commissioning Guide
Advance Outdoor Units
Installation and Commissioning Guide - Advance Split Ducted Outdoor Unit
Doc. No.0525-085 Ver. 2 22xxxx
29
PRELIMINARY DATA ONLY
Ver. 2.04 220704
THIS LABEL TO BE REMOVED ON SIGN-OFF
Circuit Breaker Size and Cable Size Requirement
Model
Circuit Breaker Size
Cable Size
*
(mm²)
Amps
MAIN
O�D� to I�D�
CRV140S/EVV140S
25.0
4.0
1.0
CRV160S/EVV160S
32.0
6.0
1.0
CRV180S/EVV180S
32.0
6.0
1.0
CRV160T/EVV160S
20.0
2.5
1.0
CRV180T/EVV180S
20.0
2.5
1.0
CRV210T/EVV210S
25.0
4.0
1.5
CRV240T/EVV240S
25.0
4.0
1.5
*
Suggested Minimum Cable Size should be used as a guide only, refer to AS/NZS 3000 “Australian / New
Zealand Wiring Rules” for more details.