Installation and Commissioning Guide - Advance Split Ducted Outdoor Unit
Doc. No.0525-085 Ver. 2 22xxxx
Installation and Commissioning Guide
Advance Outdoor Units
14
PRELIMINARY DATA ONLY
Ver. 2.04 220704
THIS LABEL TO BE REMOVED ON SIGN-OFF
CRV210T / CRV240T
671
(MTG C-C DIST)
553
112 118
59
1105
O/A
670
437
118
534
(MTG C-C DIST)
60
1685 O/A
380
565
685
O/A
COMP
OUTDOOR COIL
OUTDOOR AIR INLET
OUTDOOR
AIR INLET
295
125
1025
50
616
(MTG C-C DIST)
210.5
(MTG C-C DIST)
36.5
ELECT. ACCESS
2 x Ø 25.4mm (1")
GAS PIPE
Ø 22.2mm (7/8") SWAGED
LIQUID PIPE
Ø 12.7mm (1/2") SWAGED
25
25
OUTDOOR
AIR OUTLET
OUTDOOR
AIR INLET
A
B
C
D
30
CONDENSATION
POINTS
CONDENSATION
POINTS
** DRAWING IS SUBJECT TO CHANGE WITHOUT NOTICE**
CONDENSATION POINTS ARE DESIGNED TO ENSURE ALL
CONDENSATION IS REMOVED EFFICIENTLY TO AVOID
WATER POOLING WITHIN THE CONDENSER. IF A SINGLE
CONDENSATION DRAIN POINT IS REQUIRED, ACTRONAIR
RECOMMENDS THE INSTALLATION OF A CONDENSER
TRAY. THESE ARE AVAILABLE AS AN ADDITIONAL
ACCESSORY.
FRONT VIEW
TOP VIEW
SIDE VIEW
UNIT MODEL
NUMBER
UNIT WEIGHT
(kg)
CORNER WEIGHTS (kg)
A
B
C
D
CRV210T
200
27
53
48
72
CRV240T
209
28
56
51
74
MINIMUM SERVICE ACCESS AREAS
AND AIRFLOW CLEARANCES
HEIGHT CLEARANCE
= 1500 mm
NOTES:
1. Do not scale drawing. All dimensions are in mm
unless specified. Refer to corresponding unit
dimensional drawing for mounting hole details.
2. Service Access Areas and Spaces for Airflow Clearances given are
suggested minimum based on the condition that the spaces around
the units are free from any obstructions and a walkway passage of
1000mm between the units or between the unit and the outside
perimeter is available.
3. Minimum service access areas and spaces for airflow clearances
are responsibilities of the installer, ActronAir will not be held liable
for any extra charges incurred due to lack of access and space for
airflow.
4. Under all circumstances, condenser air must not recirculate back
onto condenser coil. Keep all clearance free of any obstructions.
5. Maximum External Static of Outdoor Fans is 5 Pa.
6. STACKING OF UNITS: Ensure that minimum airflow and clearances
are met.
7. Refer to pipe Connection Details on Specifications Sheet.
8. MTG C-C DIST = Mounting Centre to Centre Distance.
9. Use M12 bolt for feet mounting.
THIRD ANGLE
PROJECTION
B
A
300 mm
SERVICE /
AIRFLOW
CLEARANCE
800 mm
SERVICE
CLEARANCE
(COMPRESSOR
AND
ELECTRICALS)
NIL - TO - MINIMUM SERVICE CLEARANCE
C
600 mm
SERVICE / AIRFLOW CLEARANCE
COMP.
OUTDOOR COIL
D