Installation and Commissioning Guide - Advance Split Ducted Outdoor Unit
Doc. No.0525-085 Ver. 2 22xxxx
Installation and Commissioning Guide
Advance Outdoor Units
32
PRELIMINARY DATA ONLY
Ver. 2.04 220704
THIS LABEL TO BE REMOVED ON SIGN-OFF
• Diagram shown below is a general representation only. Refer to individual unit wiring diagram for complete wiring
connection details.
• Long runs beside Mains cables or TV antenna cables should be avoided where possible.
• Wiring configuration for LR7-1 and LC7-2 wall controller is the same.
• Daisy connection not allowed for NEO wall controller.
• For the Neo controllers the cable MUST be looped twice through the ferrite ring.
• Ferrite must be installed 50mm to 100mm from the CMI board.
INDOOR UNIT
OUTDOOR UNIT
1
DATA CONTROL
CABLE
3
4
AERSS
(OPTIONAL)
2a
LR7-1
WALL CONTROLLER
1
(OPTIONAL)
LR7-1
WALL CONTROLLER
2
(OPTIONAL)
LR7-1
WALL CONTROLLER
3
(OPTIONAL)
2b
2c
LM-RS-2
(OPTIONAL)
Item
Description
Maximum Cable Length
1 to 4
Outdoor PCB to Indoor PCB
100m
4 to 2a
Indoor PCB to Wall Controller 1
100m
4 to 2c
Indoor PCB to Wall Controller 3 (last controller)
75m total (Daisy Chain)**
4 to 3
Indoor PCB to Remote Sensor
100m
** Maximum Daisy Chain connection is up to 2 wall Controllers.
Description
Cable Type
Indoor to Wall Controller
Cat5e UTP (AWG 24) Data Cable
Indoor to Remote Sensor
Cat5e UTP (AWG 24) Data Cable
Indoor to Outdoor Data Cable
2 Core (1 Pair) Twisted Pair, 7/0.30 (0.5mm2) Shielded Data Cable