5. Setting up the device
Number of additional setpoints,
SPCt:
Default:
00
30 additional setpoints can be defined to the initial- and final value, so linear sensor values are
not linearised. Only activated setpoint parameters are displayed.
Setting up the physical unit,
UnIt:
Default:
no
One can choose between the above shown physical units. It will be displayed on the 5th digit of
the display.
Setting up the balance point,
Adj.pt:
Default:
08000
The balance point for the final value can be chosen from the measuring range by
su.xxx
with
0…10 V or
Sens.A
with 0…20 mA in %. The preset 80.000% result from the widespread
detuning of the melt pressure sensors. The
ADJ.PT
is only used by the sensor alignment
SE.CAL
.
Display values for setpoints,
dIS.01 … dIS.30:
Under this parameter setpoints are defined according to their value. At the sensor calibration,
like at final value/offset, one is asked at the end if a calibration shall be activated.
Setting up the tare/offset value,
tArA:
Default:
0
The given value is added to the linearized value. In this way, the characteristic line can be
shifted by the selected amount.
Rescaling the measuring input values,
OFFA:
Default:
0
With this function, you can rescale the input value of
e.g. 0.5 mV
(works setting) without
applying a measuring signal. If sensor calibration has been selected, these parameters are not
available.