ACS-CONTROL-SYSTEM GmbH
l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
21
5. Setting up the device
19
Menu group level
5.4.5. Analog output parameters for analog output 1
Menu level
Setting the final value of the analog output,
Out.En:
Default:
10000
The final value is adjusted from the smallest to the highest digit with
[
▲
] [
▼
]
and confirmed
digit per digit with
[P]
. A minus sign can only be parameterised on the highest digit. After the
last digit the device changes back into menu level.
Selection analog output,
Out.rA:
Default:
4-20
Three output signals are available 0-10 VDC, 0-20 mA and 4-20 mA. Select the desired signal
with this function.
Selection reference of analog output,
OutPt:
Default:
actua
The analog output signal can refer to different functions, in detail these are the current
measurand, the min-value, the max-value or the totaliser/sum function. If
HoLd
is selected, the
signal of the analog output will be kept. It can be continued processing after a deactivation of
Hold
. With
[P]
the selection is confirmed and the device changes into menu level.
Setting the initial value of the analog output,
Out.OF:
Default:
00000
The initial value is adjusted from the smallest to the highest digit with
[
▲
] [
▼
]
and confirmed
digit per digit with
[P]
. A minus sign can only be parameterised on the highest digit. After the
last digit the device changes back into menu level.
Parameterisation level
Menu level