5. Setting up the device

Activation  /  deactivation  of  the  programming  lock  or  completion  of  the  standard 

parameterisation with change into menu group level (complete function range),

run:

Default: 

uloc

With  the  navigation  keys 

[

]  [

]

,  choose  between  the  deactivated  key  lock 

Uloc

(works 

setting) and the activated key lock 

Loc

, or the change into the menu group level 

ProF

. Confirm 

the  selection  with 

[P]

.  After  this,  the  display  confirms  the  settings  with 

"

- - - - -"

,  and  auto-

matically switches to operating mode. If 

Loc

was selected, the keyboard is locked. To get back 

into  the  menu  level,  press 

[P]

for  3  seconds  in  operating  mode.  Now  enter  the 

CODE

(works 

setting 

1 2 3 4

) that appears using 

[

] [

]

plus 

[P]

to unlock the keyboard. 

FAIL

appears if the 

input is wrong. To parameterise further functions

ProF

needs to be set. The device confirms this

setting with

- - - - -

and changes automatically in operation mode. By pressing

[P]

for approx. 

3 seconds in operation mode, the first menu group

InP 

is shown in the display and thus confirms

the change into the extended parameterisation.  It stays activated as  long as 

ULOC

or

LOC

is

entered in menu group

RUN

.

Parameterisation level

Menu level

5.4. Extended parametrisation

(Professional operation level)

Selection of the input signal, 

TYPE:

Default: 

Su.060

There are several measuring input options: 60, 150, 300 or 1000 mV signals are available as 

works calibration (without application of the sensor signal) and 

SU 

as sensor calibration (with

the sensor applied). Confirm the selection with

[P]

and the display switches back to menu level.

Parameterisation level

Menu level

Menu group level

Menu level

5.4.1. Signal input parameters

5.3 Programming interlock „

RUN

Summary of Contents for DAL-311x3x0S

Page 1: ...unt 0 60 150 300 1000 mV 96x48 M3_12GB pdf update 14 04 2015 Technical features red display of 19999 99999 digits optional green orange or blue display minimal installation depth 120 mm without plug i...

Page 2: ...or supply 24V DC 50mA and digital input 1 Y other voltages function input 3 60 150 300 1000 mV function output A display 2 relay outputs changeover B display 4 relay outputs C display with analog outp...

Page 3: ...ent setpoint function respectively nominal value function average determination brightness control as well as the control of the digital input and the keyboard configuration 5 4 3 Safety parameters CO...

Page 4: ...the following functions are available a supply for the sensor a digital input for triggering of Hold Tara two analog outputs and interfaces for further evaluating in the unit With help of the galvani...

Page 5: ...cs controlsystem de 5 3 Electrical connection 3 3 Electrical connection Type M3 1VR5B 0002 S70BD supply of 100 240 VAC DC 10 Type M3 1VR5B 0002 W70BD supply of 10 40 VDC galv Isolated 18 30 VAC Type D...

Page 6: ...ems which are sufficent to set the device into operation are displayed To get into the professional level run through the menu level and parameterise prof under menu item RUN Menu group level complete...

Page 7: ...vice adapter The connection happens via a 4 pole micromatch plug on the back side of the device to the PC side the connection happens via an USB plug System requirements PC incl USB interface Software...

Page 8: ...igit the display switches back to the menu level If Sens was selected as input option you can only select between noca and cal With noca only the previously set display value is taken over and with ca...

Page 9: ...parameterised on the highest digit After the last digit the device changes back into menu level Selection of analog output Out rA Default 4 20 Three output signals are available 0 10 VDC 0 20 mA and...

Page 10: ...y pressing P for 3 seconds in operation mode the display shows COde and enables the user to reach all parameters by entering the A codE Under run the parameterisation can be activated permanently by s...

Page 11: ...P to unlock the keyboard FAIL appears if the input is wrong To parameterise further functions ProF needs to be set The device confirms this setting with and changes automatically in operation mode By...

Page 12: ...able Setting up the start offset value of the measuring range offs Default 0 Enter the start offset value from the smallest to the highest digit with and confirm each digit with P After the last digit...

Page 13: ...0 10 V or Sens A with 0 20 mA in The preset 80 000 result from the widespread detuning of the melt pressure sensors The ADJ PT is only used by the sensor alignment SE CAL Display values for setpoints...

Page 14: ...oints InP 01 InP 30 The setpoints are always set according to the selected input signal The desired analog values can be freely parameterised in ascending order Display overflow dI OUE Default 99999 W...

Page 15: ...ts With P the selection is confirmed and the device changes into menu level Display time DISEC Default 01 0 The display is set up with Thereby it switches up to 1 second in increments of 0 1 seconds a...

Page 16: ...value is substracted from the current measurand and the difference is evaluated in the alerting or by the analog output Thus regulations can be displayed quite easily Minimum constant value con mi Def...

Page 17: ...the correct taring by showing ooooo in the display Set tA switches into the offset value and can be changed via the navigation keys Via totAL the current value of the totaliser can be displayed for ap...

Page 18: ...vice acknowledges this with ooooo in the display EHt rE deletes the min max memory If HOLD has been selected the moment can be hold constant by pressing the O key and is updated by releasing the key A...

Page 19: ...r can be locked or released for the user En oF the initial or final value can be changed in operation mode Out EO the output signal can be changed from e g 0 20 mA to 4 20 mA or 0 10 VDC ALL analog ou...

Page 20: ...erating modes ASCII and rtu Modbus transfers no binary cycle but the ASCII Code Thus it is directly readable however the data throughput is smaller in comparison to the RTU Modbus RTU RTU Remote Termi...

Page 21: ...mA and 4 20 mA Select the desired signal with this function Selection reference of analog output OutPt Default actua The analog output signal can refer to different functions in detail these are the...

Page 22: ...y value This means that values of e g 0 mA 0 VDC or values higher than 20 mA or 10 VDC can be reached With P the selection is confirmed and the device changes into menu level Back to menu group level...

Page 23: ...the selection is confirmed and the device changes into menu level Setting the initial value of the analog output Ou2 of Default 00000 The initial value is adjusted from the smallest to the highest di...

Page 24: ...nd the setpoint display are set not set on the front of the device With P the selection is confirmed and the device changes into menu level Alarms for relay 1 CoM 1 Default a i The allocation of the a...

Page 25: ...on level Menu level Alarms for relay 5 CoM 5 Default a 5 The allocation of the alarms to relay 5 happens via this parameter one alarm or a group of alarms can be chosen With P the selection is confirm...

Page 26: ...pressing the O key on the front of the housing or by an external signal via the digital input With P the selection is confirmed and the device changes into menu level Hysteresis for threshold values H...

Page 27: ...rEt With P the selection is confirmed and the device changes into menu group level Al1 Parameterisation level Menu level The same applies for Al2 to al8 Totaliser state total Default off The totalise...

Page 28: ...al digital input Setting up the decimal point for the totaliser tot dt Default 0 The decimal point of the device can be adjusted with the navigation keys With P the selection is confirmed and the devi...

Page 29: ...To return the unit to a defined basic state a reset can be carried out to the default values The following procedure should be used Switch off the power supply Press button P Switch on voltage supply...

Page 30: ...in max value hold value totaliser value sliding average value constant value difference between instantaneous value and constant value or an activation via the digital input Alarm Relay x 7 Alarms Rel...

Page 31: ...The interface RS485 is connected via a screened data line with twisted wires Twisted Pair On each end of the bus segment a termination of the bus lines needs to be connected This is neccessary to ensu...

Page 32: ...onnected manually However the calibration will be interrupted after 30 seconds Press actuator for minimum 3 seconds For minimum 1 measuring cycle minimum 1s or maximum per actuator Current measuring r...

Page 33: ...r Measuring principle 0 1 10 0 seconds Measuring time 100 ppm K Temperature drift 92 0 0 8 x 45 0 0 6 mm Panel cut out 96x48x139 mm BxHxD incl plug in terminal Digit Measuring error Measuring range In...

Page 34: ...A 10 40 VDC galv isolated 18 30 VAC 50 60 Hz max 15 VA Power supply 250 VAC 5 AAC 30 VDC 5 ADC 30 x 103 at 5 AAC 5 ADC ohm resistive load 10 x 106 mechanically Diversity according to DIN EN50178 Chara...

Page 35: ...mobile phones or electrostatic discharge The fuse rating of the supply voltage should not exceed a value of 6A N B fuse Do not install inductive consumers relays solenoid valves etc near the device a...

Page 36: ...he default values and reconfigure the unit according to your application The word HELP lights up in the 7 segment display The input has a very low measurement check the measuring circuit With a select...

Page 37: ...ACS CONTROL SYSTEMGmbHlLauterbachstr 57lD 84307Eggenfeldenlwww acs controlsystem delinfo acs controlsystem de 37...

Page 38: ...TROL SYSTEM GmbH Lauterbachstr 57 D 84307 Eggenfelden Tel 49 0 8721 9668 0 Fax 49 0 8721 9668 30 info acs controlsystem de www acs controlsystem de Wir erwarten Ihren Anruf F llstand Pegel Druck Tempe...

Reviews: