22
Plumbing the System
1
1) (Optional) Install a pressure regulator (not supplied) if system pressure exceeds
65 psi. A pressure regulator is required upstream of the Aclarus Ozone Water
System if the supply pumps and pressure can exceed 65 psi. Set pressure
regulator to maintain incoming pressure to the system below 65 psi. Refer
“Bypass Valves and Pressure Regulators”.
2) Optionally, the owner can install a ball valve and drain after the last filter for
easier flushing of filters. With a hose connection on the drain the flush process
can be completed more easily.
3) Ensure filters are full of appropriate media or if using a cartridge that is flushed and
placed in proper order:
ten micron sediment filter before ozone system (optional/recommended)
activated carbon after ozone system
NOTE: If two post filters are required, the first filter is a sediment filter or a
Nextsand or Birm Filter (for iron) and the second filter is the Activated Carbon
filter. Be sure to place the Activated Carbon after the ozone system.
4) Plumb Aclarus system and other components into water supply. See
“Components
Layout” (Page 9). Components may vary depending on the application.
5) Complete the following:
Attach 0.25
” PVC braided hose to the outlet of each gas-off chamber
Connect gas-
offs with a 0.25” hose barb tee
Vent gas-off chambers to exterior of dwelling or approximately 60 cm (two
feet) down an atmospheric floor drain
6) Ensure overflow protection (if required) is attached properly.
7) Connect the air dryer line to the Aclarus Ozone Enclosure incoming air
line. This line feeds ambient air to the ozone generator.
8)
Ensure 0.25” braided hose and air-line check valve are installed between
the ozone generator discharge and mazzei. Ensure Check Valve installed
in proper direction for air flow from ozone generator to mazzei.
NOTE
: Make sure colour change silica in the tube is orange to start and when more
than 75% changes to green to replace and recharge as directed in this manual (page
22).
1
OPTIONAL:
Install bypass valves upstream of the system to allow uninterrupted water supply during system
servicing. See diagram “Bypass Valves and Pressure Regulators”.
Summary of Contents for AOWT-7
Page 9: ...9 System Components...
Page 10: ...10 NOTE System components and tank may not be exactly as shown...
Page 47: ...47 Appendix Component Specification Sheets Pumps Specifications...
Page 48: ...48...
Page 49: ...49...
Page 50: ...50 Flow Switch Specifications...
Page 51: ...51...
Page 52: ...52 Mazzei Specifications...
Page 53: ...53 Gas Off 1 Specifications...