SGM3000 Series Smart Meters
User Manual
Restricted
GEH-7111-1.00-2
81
Register Function:
Unchanged
Program:
OK
TOU schedule:
OK
TOU calendar:
OK
Billing Data:
Corrupt data
Caution Reporting
The meter also checks other conditions that are of concern but do not indicate a problem with
the meter hardware. The meter reports these as cautions. Individual cautions may be enabled
or disabled selectively. If a caution is enabled, it can be configured to be displayed and
optionally freeze the display.
Low battery, loss of program, and un-programmed cautions are used to remind the user of
actions that are required. Any meter with a low battery caution may lose time if the battery is
not replaced before the next power outage.
Other caution codes report unusual operation such as receiving energy from the load, leading
power factor, very high current flow, or low voltage.
Note:
When multiple cautions occur they are combined. For example, CA 040 400 indicates
leading quadergy and low potential.
Table 13 Caution Code Display
Caution Display
Probable Cause
Remedy
CA 000 001
a. Low battery
b. Battery failed test
Organize replacement meter and meter
return.
CA 000 010
a. Meter un-programmed
b. Using default values
Program the meter.
CA 000 040
a. Loss of program
b. Programming interrupted
c.
Using previous values
Program the meter.
CA 000 050
a. Loss of program and Meter is un-
programmed.
b. Programming interrupted
c.
Using default values
Program the meter.
CA 000 400
Low potential on phase A
Check circuit voltage.
CA 004 000
Demand overload warning has exceeded
programmed threshold.
a. Check for service overload
conditions.
b. Check programming threshold value.
CA 040 000
Leading kvarh warning
a. Disable the warning.
b. Check system operating parameters
if leading kvarh is unexpected.