2.3 Zenith ZTG series features
Feature comparison
ZTG(D) controls (LCD)
l
ON
ll
ON
Auto
Alarm reset
AUTO
!
S1
S2
LOAD
l
ll
O
O
OFF
Esc
l
ON
ll
ON
Auto
Alarm reset
AUTO
!
S1
S2
LOAD
l
ll
Esc
Ampere sizes available
UL: 30...1200 A
Rated voltage
200...480 Vac
Rated frequency
50 / 60 Hz
Phase system
Single and Three
Number of poles
2, 3 and 4
Neutral configuration
Switched
Yes
Product type
Open transition (I-II)
Yes
Delayed transition (I - O - II or II - O - I)
Yes
Voltage and frequency settings
Pick up SOURCE 1 Voltage
81…99%, 101…119%
Drop out SOURCE 1 Voltage
80…98%, 102…120%
Pick up SOURCE 2 Voltage
81…99%, 101…119%
Drop out SOURCE 2 Voltage
80…98%, 102…120%
Pick up SOURCE 1 Frequency
80,5…99,5%, 100,5…119,5%
Drop out SOURCE 1 Frequency
80…99%, 101…120%
Pick up SOURCE 2 Frequency
80,5…99,5%, 100,5…119,5%
Drop out SOURCE 2 Frequency
80…99%, 101…120%
Time delay settings
Override momentary SOURCE 1 Outage, sec
0…60
Transfer from SOURCE 1 to SOURCE 2, sec
0…3600
Override momentary SOURCE 2 Outage, sec
0…60
Transfer from SOURCE 2 to SOURCE 1, min
0…120
Generator stop delay, min
0…60
Center-OFF delay, sec
0…300
Summary of Contents for Zenith ZTG 30
Page 2: ......
Page 6: ...6 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE 1 ...
Page 10: ...10 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE 1 ...
Page 52: ...52 1 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...
Page 91: ...91 1 Fig 7 3 ZTGD delayed transition circuit diagram ...
Page 93: ...93 1 Figure A Figure B ...
Page 94: ...94 1 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE Figure C ...
Page 96: ...2 96 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...
Page 108: ...2 108 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...
Page 114: ...2 114 Zenith ZTG Series ATS OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...