The available measured values of an IED are depending on the
actual hardware (TRM) and the logic configuration made in
PCM600.
Measurement function application for a 400kV OHL
SEMOD54481-12 v11
Single line diagram for this application is given in figure
:
400kV Busbar
400kV OHL
P
Q
1000/1 A
IEC09000039-3-en.vsdx
IED
kV
3
1
,
0
/
3
400
IEC09000039-1-EN V3 EN-US
Figure 97:
Single line diagram for 400kV OHL application
In order to monitor, supervise and calibrate the active and reactive power as
indicated in figure
it is necessary to do the following:
1. Set correctly CT and VT data and phase angle reference channel
PhaseAngleRef
“Setting of the phase reference channel”
PCM600 for analog input channels
2. Connect, in PCM600, measurement function to three-phase CT and VT inputs
3. Set under General settings parameters for the Measurement function:
•
general settings as shown in table
.
•
level supervision of active power as shown in table
.
•
calibration parameters as shown in table
.
1MRK 504 169-UEN A
Section 13
Monitoring
Transformer protection RET650 2.2 IEC
273
Application manual
Summary of Contents for ret650
Page 1: ...RELION 650 SERIES Transformer protection RET650 Version 2 2 Application manual...
Page 2: ......
Page 28: ...22...
Page 38: ...32...
Page 42: ...36...
Page 80: ...74...
Page 168: ...162...
Page 174: ...168...
Page 250: ...244...
Page 346: ...340...
Page 366: ...360...
Page 390: ...384...
Page 391: ...385...