Figure 127:
Configuration for using an instance in task time group 2 as DFT
reference.
Assume instance SMAI4:16 in task time group 2 has been selected in the
configuration to control the frequency tracking for all instances. Observe that the
selected reference instance (i.e. frequency tracking master) must be a voltage type.
Observe that positive sequence voltage is used for the frequency tracking feature.
For task time group 1 this gives the following settings (see Figure
numbering):
SMAI1:1 – SMAI12:12:
DFTReference
=
ExternalDFTRef
to use DFTSPFC input
as reference (SMAI4:16)
For task time group 2 this gives the following settings:
SMAI1:13:
DFTRefExtOut
=
DFTRefGrp4
to route SMAI4:16 reference to the
SPFCOUT output,
DFTReference
=
DFTRefGrp4
for SMAI1:13 to use SMAI4:16
) SMAI2:14 – SMAI12:24:
DFTReference
=
DFTRefGrp4
to use SMAI4:16 as reference.
For task time group 3 this gives the following settings:
SMAI1:25 – SMAI12:36:
DFTReference
=
ExternalDFTRef
to use DFTSPFC
input as reference (SMAI4:16)
Section 18
1MRK 504 169-UEN A
Basic IED functions
352
Transformer protection RET650 2.2 IEC
Application manual
Summary of Contents for ret650
Page 1: ...RELION 650 SERIES Transformer protection RET650 Version 2 2 Application manual...
Page 2: ......
Page 28: ...22...
Page 38: ...32...
Page 42: ...36...
Page 80: ...74...
Page 168: ...162...
Page 174: ...168...
Page 250: ...244...
Page 346: ...340...
Page 366: ...360...
Page 390: ...384...
Page 391: ...385...