12.13.2
Application
GUID-4C6D730D-BB1C-45F1-A719-1267234BF1B9 v1
The function gives the possibility to monitor the level of integer values in the
system relative to each other or to a fixed value. It is a basic arithmetic function
that can be used for monitoring, supervision, interlocking and other logics.
12.13.3
Setting guidelines
GUID-ADA3E806-BEF1-4D15-B270-207386A0AEE4 v2
For proper operation of comparison the set value should be set within the range of
± 2 ×10
9
.
Setting procedure on the IED:
EnaAbs
: This setting is used to select the comparison type between signed and
absolute values.
•
Absolute
: Comparison is performed on absolute values of input and reference
values
•
Signed
: Comparison is performed on signed values of input and reference
values.
RefSource
: This setting is used to select the reference source between input and
setting for comparison.
•
Input REF
: The function will take reference value from input REF
•
Set Value
: The function will take reference value from setting
SetValue
SetValue
: This setting is used to set the reference value for comparison when
setting
RefSource
is selected as
SetValue
.
12.13.4
Setting example
GUID-13302FD6-1585-42FE-BD6D-44F231982C59 v2
For absolute comparison between inputs:
Set the
EnaAbs
=
Absolute
Set the
RefSource
=
Input REF
Similarly for Signed comparison between inputs
Set the
EnaAbs
=
Signed
Set the
RefSource
=
Input REF
For absolute comparison between input and setting
Set the
EnaAbs
=
Absolute
1MRK 504 169-UEN A
Section 12
Logic
Transformer protection RET650 2.2 IEC
263
Application manual
Summary of Contents for ret650
Page 1: ...RELION 650 SERIES Transformer protection RET650 Version 2 2 Application manual...
Page 2: ......
Page 28: ...22...
Page 38: ...32...
Page 42: ...36...
Page 80: ...74...
Page 168: ...162...
Page 174: ...168...
Page 250: ...244...
Page 346: ...340...
Page 366: ...360...
Page 390: ...384...
Page 391: ...385...