REFPDIF
I3PW1CT1
I3P
IdN/I
I3PW1CT2
Protected
winding
IEC09000113-3.vsd
IEC09000113-3 V2 EN-US
Figure 38:
Connection of Restricted earth fault, low impedance function
REFPDIF in multi-breaker arrangements
6.2.2.6
CT earthing direction
M13048-29 v13
To make the restricted earth fault protection REFPDIF operate correctly, the main
CTs are always supposed to be star -connected. The main CT's neutral (star)
formation can be positioned in either way,
ToObject
or
FromObject
. However,
internally REFPDIF always uses reference directions towards the protected
transformers, as shown in Figure
. Thus the IED always measures the primary
currents on all sides and in the neutral of the power transformer with the same
reference direction towards the power transformer windings.
The earthing can be freely selected for each of the involved current transformers.
6.2.3
Setting guidelines
IP14942-1 v1
6.2.3.1
Setting and configuration
M13052-3 v3
Recommendation for analog inputs
M13052-8 v10
I3P: Neutral point current ( All analog inputs connected as 3Ph groups in ACT).
I3PW1CT1: Phase currents for winding 1 first current transformer set.
I3PW1CT2: Phase currents for winding1 second current transformer set for multi-
breaker arrangements. When not required configure input to "GRP-OFF".
I3PW2CT1: Phase currents for winding 2 first current transformer set. Used for
autotransformers.
Section 6
1MRK 504 169-UEN A
Differential protection
98
Transformer protection RET650 2.2 IEC
Application manual
Summary of Contents for ret650
Page 1: ...RELION 650 SERIES Transformer protection RET650 Version 2 2 Application manual...
Page 2: ......
Page 28: ...22...
Page 38: ...32...
Page 42: ...36...
Page 80: ...74...
Page 168: ...162...
Page 174: ...168...
Page 250: ...244...
Page 346: ...340...
Page 366: ...360...
Page 390: ...384...
Page 391: ...385...