13.5.3
Setting guidelines
IP14841-1 v1
M12811-3 v3
The input parameters for the Event function (EVENT) can be set individually via
the local HMI (
Main Menu/Settings / IED Settings / Monitoring / Event
Function
) or via the Parameter Setting Tool (PST).
EventMask (Ch_1 - 16)
M12811-5 v3
The inputs can be set individually as:
•
NoEvents
•
OnSet
, at pick-up of the signal
•
OnReset
, at drop-out of the signal
•
OnChange
, at both pick-up and drop-out of the signal
•
AutoDetect
, the EVENT function makes the reporting decision (reporting
criteria for integers have no semantic, prefer to be set by the user)
LONChannelMask or SPAChannelMask
M12811-15 v2
Definition of which part of the event function block that shall generate events:
•
Off
•
Channel 1-8
•
Channel 9-16
•
Channel 1-16
MinRepIntVal (1 - 16)
M12811-29 v3
A time interval between cyclic events can be set individually for each input
channel. This can be set between 0 s to 3600 s in steps of 1 s. It should normally be
set to 0, that is, no cyclic communication.
M12811-34 v1
It is important to set the time interval for cyclic events in an
optimized way to minimize the load on the station bus.
13.6
Disturbance report DRPRDRE
IP14584-1 v2
13.6.1
Identification
M16055-1 v8
Function description
IEC 61850 identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Disturbance report
DRPRDRE
-
-
Disturbance report
A1RADR - A4RADR
-
-
Disturbance report
B1RBDR - B22RBDR
-
-
1MRK 504 169-UEN A
Section 13
Monitoring
Transformer protection RET650 2.2 IEC
285
Application manual
Summary of Contents for ret650
Page 1: ...RELION 650 SERIES Transformer protection RET650 Version 2 2 Application manual...
Page 2: ......
Page 28: ...22...
Page 38: ...32...
Page 42: ...36...
Page 80: ...74...
Page 168: ...162...
Page 174: ...168...
Page 250: ...244...
Page 346: ...340...
Page 366: ...360...
Page 390: ...384...
Page 391: ...385...