To ensure proper application of the IED for this power transformer it is necessary
to do the following:
1. Check that HV & LV CTs are connected to 5 A CT inputs in the IED.
2. For second solution make sure that LV delta connected CTs are DAB connected.
3. For star connected CTs make sure how they are 'star'red (that is, earthed) to/from
protected transformer.
4. Enter the following settings for all three CT input channels used for the HV side
CTs, see table
Table 13:
CT input channels used for the HV side CTs
Setting parameter
Selected value for both solutions
CTprim
400
CTsec
5
CTStarPoint
ToObject
5. Enter the following settings for all three CT input channels used for the LV side
CTs, see table
"CT input channels used for the LV side CTs"
.
CT input channels used for the LV side CTs
Setting parameter
Selected value for Solution 1 (star
connected CT)
Selected value for Solution 2
(delta connected CT)
CTprim
1500
1500
866
3
=
EQUATION1889 V1 EN-US
(Equation 13)
CTsec
5
5
CTStarPoint
ToObject
ToObject
To compensate for delta connected CTs, see equation
.
6. Enter the following values for the general settings of the differential protection
function, see table
.
Table 14:
General settings of the differential protection
Setting parameter
selected value for both Solution 1
(star conected CT)
Selected value for both
Solution 2 (delta connected
CT)
RatedVoltageW1
115 kV
115 kV
Rated VoltageW2
24.9 kV
24.9 kV
RatedCurrentW1
301 A
301 A
RatedCurrentW2
1391 A
1391 A
Table continues on next page
Section 6
1MRK 504 169-UEN A
Differential protection
90
Transformer protection RET650 2.2 IEC
Application manual
Summary of Contents for ret650
Page 1: ...RELION 650 SERIES Transformer protection RET650 Version 2 2 Application manual...
Page 2: ......
Page 28: ...22...
Page 38: ...32...
Page 42: ...36...
Page 80: ...74...
Page 168: ...162...
Page 174: ...168...
Page 250: ...244...
Page 346: ...340...
Page 366: ...360...
Page 390: ...384...
Page 391: ...385...