Figure
shows an application example of how the user can connect
SINGLECMD via configuration logic circuit to control a high-voltage apparatus.
This type of command control is normally carried out by sending a pulse to the
binary outputs of the IED. Figure
shows a close operation. An open breaker
operation is performed in a similar way but without the synchro-check condition.
Single
command
function
SINGLECMD
CMDOUTy
OUTy
Close CB1
&
User-
defined
conditions
Synchro-
check
Configuration logic circuits
en04000206.vsd
IEC04000206 V2 EN-US
Figure 87:
Application example showing a logic diagram for control of a circuit
breaker via configuration logic circuits
Figure
and figure
show other ways to control functions, which require steady
On/Off signals. Here, the output is used to control built-in functions or external
devices.
1MRK 504 169-UEN A
Section 11
Control
Transformer protection RET650 2.2 IEC
241
Application manual