16.4.2.1
Identification
GUID-1A6E066C-6399-4D37-8CA5-3074537E48B2 v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Multiple command and receive
MULTICMDRCV
-
-
Multiple command and send
MULTICMDSND
-
-
16.4.2.2
Application
M14790-3 v5
The IED provides two function blocks enabling several IEDs to send and receive
signals via the interbay bus. The sending function block, MULTICMDSND, takes
16 binary inputs. LON enables these to be transmitted to the equivalent receiving
function block, MULTICMDRCV, which has 16 binary outputs.
16.4.2.3
Setting guidelines
SEMOD119915-1 v1
Settings
M14789-4 v3
The parameters for the multiple command function are set via PCM600.
The
Mode
setting sets the outputs to either a
Steady
or
Pulsed
mode.
16.5
SPA communication protocol
IP14614-1 v1
16.5.1
Application
IP14785-1 v1
SEMOD115767-5 v6
SPA communication protocol is an alternative to IEC 60870-5-103, and they use
the same rear communication port.
When communicating with a PC connected to the utility substation LAN via WAN
and the utility office LAN (see Figure
), and when using the rear optical
Ethernet port, the only hardware required for a station monitoring system is:
•
Optical fibres from the IED to the utility substation LAN
•
PC connected to the utility office LAN
1MRK 504 169-UEN A
Section 16
Station communication
Transformer protection RET650 2.2 IEC
325
Application manual
Summary of Contents for ret650
Page 1: ...RELION 650 SERIES Transformer protection RET650 Version 2 2 Application manual...
Page 2: ......
Page 28: ...22...
Page 38: ...32...
Page 42: ...36...
Page 80: ...74...
Page 168: ...162...
Page 174: ...168...
Page 250: ...244...
Page 346: ...340...
Page 366: ...360...
Page 390: ...384...
Page 391: ...385...