![background image](http://html1.mh-extra.com/html/abb/relion-sam600-io/relion-sam600-io_operation-manual_3395302063.webp)
1.
To set the IED to test mode, select
Main menu/Test /IED test mode/TESTMODE:1
and
set the parameter
TestMode
to
On
.
2.
To operate or force the output relay to operate, select
Main menu/Test/Forcing /Binary
output values
and then navigate to the board with the actual binary output relay to be
operated/forced.
3.
Select the BOn to be operated/forced and use
and
or
to operate the actual
output relay.
Each BOn is represented by two signals. The first signal in LHMI is the actual value 1 or 0
of the output, and in PCM600 a lit or dimmed diode. The second signal is the status
Normal or Forced. Forced status is only achieved when the BO is set to
Forced
or
operated on the LHMI.
Set the parameter
TestMode
to
Off
after completing these tests. The Start
LED stops flashing when the relay is no longer in test mode.
An initially high contact resistance does not cause problems as it is reduced quickly by the electrical
cleaning effect of fritting and thermal destruction of layers, bringing the contact resistance back to the
mOhm range. As a result, practically the full voltage is available at the load.