IEC17000246-1-en.vsd
IEC17000246 V1 EN-US
Figure 32:
Clear view
The content of the Clear menu depends on the configuration configured with PCM600.
2.
Select the item to be cleared with
or
.
3.
Press
, select OK to confirm the selection or Cancel to cancel the selection.
4.
To clear other items, repeat the steps.
7.3
Changing the IED functionality
7.3.1
Defining the setting group
GUID-A9853F1B-78ED-4AEF-AAE2-C27FF3DAE408 v3
Do not switch off the auxiliary power supply to the IED before changes. For example,
when setting parameter changes are saved.
7.3.1.1
Activating a setting group
AMU0600439 v8
IED settings are planned in advance for different operation conditions by calculating setting values to
different setting groups. The active setting group can be changed manually from the menu or by the
PCM600 tool.
1.
Select
Main menu /Settings /Active setting group /SETGRPS:1
and press
.
Section 7
1MRK 500 131-UEN Rev. C
Operating procedures
46
Switchgear control unit SAM600-IO
Operation manual