IEC13000261-1-en.vsd
GUID-D18A9DC0-4392-4BAF-86D0-C43F2714B428 V1 EN-US
Figure 28:
Manual triggering
The disturbance recorder is now triggered.
7.1.2.2
Monitoring disturbance recorder data
GUID-CBA8221F-A0F8-4043-98D7-577830F29F7F v6
Read individual disturbance recordings from the IED with the PCM600 software to monitor
disturbance recorder data.
1.
Select
Main menu /Disturbance records
.
All disturbance records are listed.
2.
Scroll the view with
or
.
IEC13000262-1-en.vsd
GUID-ACB5A57F-394B-475B-96C0-7C515A530D1F V1 EN-US
Figure 29:
Monitoring disturbance recorder via the LHMI
3.
To view a specific disturbance record, press
.
A list of detail categories is displayed.
1MRK 500 131-UEN Rev. C
Section 7
Operating procedures
Switchgear control unit SAM600-IO
43