Document all changes to parameter settings.
For more information, see PCM600 documentation.
6.3.1
IED settings for IED functionality
GUID-A0878EB9-66F3-4839-AE1C-C41AB9463271 v4
Function settings can be edited one by one by navigating to the individual setting values, for example
via the LHMI. The values in other setting groups should be known before editing a certain setting
value.
After completing the editing of setting group values, the new values are activated. The user can
either commit the edited values or discard them.
6.3.2
IED settings for different operating conditions
GUID-7328A918-CE00-4F97-B51F-FD7FC63FD30D v5
IED settings can be designed for various operation conditions by defining different setting values to
different setting groups. The active setting group can be changed by the IED application or manually
via the LHMI or PCM600.