Figure 27:
Fault indication
The internal event list is not updated dynamically. To update the list, leave the
Internal events
menu and then select it again.
7.1.2
Recorded data
GUID-1E9CFEC1-6245-4612-B637-821951B95D60 v7
The IED is provided with intelligent and flexible functionality that collects different kinds of data. The
recorded data gives substantial information for post fault analysis.
•
Disturbance records
•
Events
7.1.2.1
Creating disturbance recordings
GUID-B0CE46C1-1219-4BA2-9627-E53FC0413409 v5
Normally disturbance recordings are triggered by the IED applications but the recording can also be
triggered manually.
Set the DRPRDRE
Operation
to
On
via LHMI or PCM600 and at least one channel
has to be connected. To make the setting, select
Main menu /Settings /IED
Settings
and then
Monitoring /Disturbance report /DisturbanceReport /
DRPRDRE:1
.
1.
Select
Main menu /Disturbance records
.
2.
Select
Manual Trig
with
or
.
3.
Press
to execute manual triggering.