Section 9
Testing functionality by secondary
injection
9.1
Testing disturbance report
9.1.1
Introduction
M17101-2 v6
The following sub-functions are included in the disturbance report function:
•
Disturbance recorder
•
Event list
•
Event recorder
•
Fault locator
•
Trip value recorder
•
Indications
If the disturbance report is set on, then its sub-functions are also set up and so it is
not possible to only switch these sub-functions off. The disturbance report function
is switched off (parameter
Operation
=
Off
) in PCM600 or the local HMI under
Main menu/Settings/IED Settings/Monitoring/Disturbance report/DRPRDRE:
1
.
9.1.2
Disturbance report settings
M11746-2 v6
When the IED is in test mode, the disturbance report can be made active or
inactive. If the disturbance recorder is turned on during test mode, recordings will
be made. When test mode is switched off all recordings made during the test
session are cleared.
Setting
OpModeTest
for the control of the disturbance recorder during test mode
are located on the local HMI under
Main menu/Settings/IED Settings/
Monitoring/Disturbance report/DRPRDRE:1
.
9.1.3
Disturbance recorder (DR)
M11750-2 v6
A
Manual Trig
can be started at any time. This results in a recording of the actual
values from all recorded channels.
The
Manual Trig
can be started in two ways:
1. From the local HMI under
Main menu/Disturbance records
.
1.1. Enter on the row at the bottom of the HMI called
Manual trig
.
1MRK 506 383-UEN A
Section 9
Testing functionality by secondary injection
Line distance protection REL650 2.2 IEC
71
Commissioning manual
Summary of Contents for REL650 series
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Commissioning manual...
Page 2: ......
Page 24: ...18...
Page 28: ...22...
Page 38: ...32...
Page 54: ...48...
Page 58: ...52...
Page 178: ...172...
Page 182: ...176...
Page 188: ...182...
Page 196: ...190...
Page 206: ...200...
Page 207: ...201...