4.
Verify that phase selection re-trip (if selected) and back-up trip are achieved
after set times. Failure to trip is simulated by keeping the signal(s) CB closed
activated.
5.
Disconnect the input signal and the START signal(s). Keep the CB closed
signal(s).
6.
Apply the fault and the start again. The value of current should be below the
set value
I>BlkCont
.
7.
Arrange disconnection of BC closed signal(s) well before set back-up trip
time
t2
. It simulates a correct CB tripping.
8.
Verify that back-up trip is not achieved. Re-trip can appear for example, due
to selection “Re-trip without current check”.
9.4.7.8
Completing the test
M12104-72 v5
Continue to test another function or end the test by changing the
TESTMODE
setting to
Off
. Restore connections and settings to their original values, if they were
changed for testing purposes.
9.4.8
Pole discordance protection CCPDSC
SEMOD55625-59 v6
Prepare the IED for verification of settings outlined in Section
9.4.8.1
Verifying the settings
SEMOD55625-63 v8
1.
External detection logic, Contact function
selection
=
ContSel
setting equals
CCPDSC signal from CB. Activate the EXTPDIND binary input, and
measure the operating time of CCPDSC.
Use the TRIP signal from the configured binary output to stop the timer.
2.
Compare the measured time with the set value
tTrip
.
3.
Reset the EXTPDIND input.
4.
Activate the BLKDBYAR binary input.
This test should be performed together with Autorecloser SMBRREC.
5.
Activate the EXTPDIND binary input.
No TRIP signal should appear.
6.
Reset both BLKDBYAR and EXTPDIND binary inputs.
7.
Activate the BLOCK binary input.
8.
Activate EXTPDIND binary input.
NO TRIP signal should appear.
9.
Reset both BLOCK and EXTPDIND binary inputs.
10. If Internal detection logic Contact function
selection
=
ContSel
setting equals
Pole position from auxiliary contacts. Then set inputs
POLE1OPN...POLE3CL in a status that activates the pole discordance logic
and repeats step 2 to step
Section 9
1MRK 506 383-UEN A
Testing functionality by secondary injection
118
Line distance protection REL650 2.2 IEC
Commissioning manual
Summary of Contents for REL650 series
Page 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Commissioning manual...
Page 2: ......
Page 24: ...18...
Page 28: ...22...
Page 38: ...32...
Page 54: ...48...
Page 58: ...52...
Page 178: ...172...
Page 182: ...176...
Page 188: ...182...
Page 196: ...190...
Page 206: ...200...
Page 207: ...201...