5 - Installation
• Once the phase of mechanical installation of the METER is finished, it
is necessary to configure the METER in order to make it compatible with
the REACT system. Set the parameters of the meter as set out in the
table:
Parameter
Settings
Address
1
Protocol
MODBUS
Baud rate
57600
Parity
EVEN
The settings are made by using the keypad and the display on the meter:
1. Press for two seconds to access the setup menu of the meter.
2. Press repeatedly until the display shows “
Set
”.
- Press
to confirm.
3. Press repeatedly until the display shows “
RS-485
”.
- Press
to confirm.
4. Press repeatedly until the display shows “
Protocol
”.
- Press to access.
- Press
to enable the change in the value.
- Press repeatedly until the display shows “
Modbus
”.
- Press
to confirm the change.
- Press for two seconds to return to the RS485 menu.
5. Press repeatedly until the display shows “
Baud rate
”.
- Press to access.
- Press
to enable the change in the value.
- Press repeatedly and select 57600.
- Press
to confirm the change.
- Press for two seconds to return to the RS485 menu.
6. Press repeatedly until the display shows “
Address
”.
- Press to access.
- Press
to enable the change in the value.
- Press repeatedly and select 1.
- Press
to confirm the change.
- Press for two seconds to return to the RS485 menu.
7. Press repeatedly until the display shows “
Modbus
”.
- Press to access.
- Press
to enable the change in the value.
- Press repeatedly and select even.
- Press
to confirm the change.