7 - Operation
This means that during the absence of grid voltage (display message
"Missing Grid") the alarm contact remains in its resting position.
• Crepuscular (display text “Crepuscular”)
Vin > Vstart
Vin < Vstart
GRID RECONNECTION
t=based on Country Standard
Vin
IS STILL LESS THAN
Vstart
Yes
No
N.C.
N.O.
N.C.
N.O.
N.C.
N.O.
Relay State:
Idle
Relay State: Switched
Relay State:
Idle
The relay is activated (status: switched)
as soon as the inverter input voltage
exceeds the activation voltage set.
The relay is in its rest position when the
input voltage drops below 70% of the acti-
vation voltage set.
This mode is useful for disconnecting any
output transformers that could have unne-
cessary consumption during the night.
• Alarm Latch (display text “Alarm Latch”)
INVERTER RUN
ERROR OCCURENCY
ERROR MESSAGE
t=15s
GRID RECONNECTION
t=based on Country Standard
ERROR
STILL
PRESENT
Yes
No
N.C.
N.O.
N.C.
N.O.
Relay State:
Idle
Relay State: Switched
N.C.
N.O.
Relay State: Switched
The relay is activated (status: switched)
whenever an error (code Exxx) or a
warning (code Wxxx) is present (see
the table below). The contact returns to
its resting position when the inverter re-
turns to its normal operating state and
reconnects to the grid.
Alarms for which the relay is activated
E001
E002
E003
E004
E005
E006
E007
E009
E010
E011
E012
E013
E014
E015
E016
E017
E018
E019
E020
E021
E022
E023
E024
E025
E026
E027
E028
E029
E030
E031
E032
E033
E034
E035
E036
E037
E046
E050
E053
E054
E055
E056
E057
E058
E077
E078
E081
E084
E089
W003
W004
W005
W006
W007
> Statistics
> Self consumpti.
> Self sufficien.
> Ener. from grid
> Ener. to grid
> Ener. to load
> PV en. to load
> PV ener.
> Settings
> Info
> Measures
> Set time
Password 0000
> Set cash
> Set RS485 com
> Country Select
> New password
> SD Update Info
> Energy Policy
Inverter
> Statistics
> Settings
> Vstart
> Input mode
> Input UV Delay
> Service
> Info
> Part No.
> Serial No.
> Firmware
> Remote ON/OFF
> MPPT Scan
> Power Limit.
> Reactive Power
> Autotest
> Alarms
> Backup
> Lifetime
> Partial
> Today
> Last 7 days
> Last 30 days
> Last 365 days
> User Period
Display
> Settings
> Backlight
> Contrast
> Buzzer
> Power Graph
> Language
Meter
> Settings
> Info
> Type
> Part No.
> Serial No.
> FW Rel.
> Measures
> Voltage
> Active Power
> Line current
> Load current
> Frequency
> Meter model
> Meter Address
> Meter com
Battery
> General
**
****
Load Manager
> info
> Relay Status
****
WIFI Logger
> Settings
> Info
> Part No.
> Serial No.
> View IP
> View Mode
> Restore AP
*
System
****
Password 0000
Password 0000
Password 0000
> Settings
> Info
> Nom. Cap
> Measures
> Ibat
> Vbat
> Pbat
> RE
> SOC
> SOH
> RT
> Battery Model
> Battery Packs
Password 0000
> Pack 1
> Settings
> Info
> Device Name
> Serial No.
> FW Rel.
> Nom. Capacity
> Init. Capacity
> Status
> Warning
> Alarms
> Measures
> Pack 1 enable
> Smoke Sensor
Password 0000
> Statistics
> Energy dischar.
> E-day
> E-7d
> E-30d
> E-365
> E-tot
> Ibat
> Vbat
> Pbat
> Tbat
> FCC
> RC
> RE
> TED
> SOC
> SOH
> TUT
> TDT
> RT
> CC