5 - Installation
E
nvironmental checks
The installation location must comply with the requirements of the
standards EN 50272-2 and EN 60069-10.
• The installation location must be easily accessible
• Prevent access to the installation location by children
• The minimum air volume in the installation location must be 15m
3
and equipped with two openings with a diameter of 6cm for natural air
circulation. If the two openings are located in the same wall they must be
made at a minimum distance of 2 metres from each other.
• Installation of the unit in a location exposed to solar rays must be
avoided as it may cause:
- power limitation phenomena in the inverter (with a resulting decreased
energy production by the system)
- premature wear of the electrical/electromechanical components
- premature wear of the mechanical components (gaskets) and of the
user interface (display)
- reduction in performance, lifetime and possible damage of the battery
pack
• Always ensure that the flow of air around the inverter is not blocked so
as to prevent overheating.
• Do not install in locations where flammable substances or gases may
be present
• Do not install in locations with a constant presence of water and/or high
humidity level.
• Do not install in rooms where people live or where the prolonged
presence of people or animals is expected, because of the noise (around
50dB(A) at 1 m) that the inverter produces during operation.
2m
Ø 6cm
Ø 6cm
>15m
3
60cm
60cm
60cm
60cm