![ABB REACT-3.6-TL Product Manual Download Page 23](http://html.mh-extra.com/html/abb/react-3-6-tl/react-3-6-tl_product-manual_4163023.webp)
- 23 -
000552AG
2 - Characteristics
Photovoltaic inverter with integrated charger
REACT-UNO-3.6-TL
REACT-UNO-4.6-TL
Back-up output protection
Maximum AC overcurrent protection
16 A
Operating performance
Maximum efficiency (ηmax)
97.1%
Weighted efficiency (EURO/CEC)
96.6% / -
Typical battery efficiency (full cycle)
94.0%
Communication
Remote monitoring
Integrated Wi-Fi datalogger
Wireless local monitoring
Wi-Fi with UI webserver, mobile APP
User interface
Mobile APP, UI Webserver, Graphic display
Wired local monitoring
PVI-USB-RS232_485 (opt.)
Environmental
Ambient temperature
-20...+55°C
Optimal operating temperature for battery
+5...+35°C
Operating temperature for battery - charge
0...+40°C
Operating temperature for battery - discharge
-10...+45°C
Relative humidity
5…95% without condensation
(when used without battery 4…100% condensing)
Noise emission pressure, typical
50dB @ 1m
Maximum operating altitude without derating
2000 m / 6560 ft
Recommended location
Internal with ventilation
Physical
Degree of environmental protection
IP54 (REACT-UNO), IP21 (REACT-BATT-AP1)
3)
Cooling system
Natural
Size (H x W x D), equipped with 1 REACT-BATT-AP1
740 mm x 985 mm x 231 mm
Weight (REACT-UNO and REACT-BATT-AP1)
< 67 kg
Assembly system
Wall bracket
Safety
Insulation level
Transformerless
Marking
CE
Safety and EMC Standards
IEC/EN62109-1, IEC/EN62109-2, EN61000-6-2,
EN61000-6-3, EN61000-3-2, EN61000-3-3,
EN61000-3-11, EN61000-3-12
Grid Standard
(check availability through the sales channel)
CEI 0-21, DIN V VDE V 0126-1-1, VDE-AR-N 4105,
G83/2, G59/3, VFR2014, 4777.2:2015
Other characteristics
Load management
Yes, through load manager box
AC back-up output, off grid
Yes, automatic or manual restart in the case of no grid
Grid support
Yes, where required by the regulations
1) The output voltage range may vary according to the grid standard of the country of installation
2) The output frequency range may vary according to the grid standard of the country of installation
3) The IP54 protection level is guaranteed by complying with the indications set out in this manual and listed here below:
• in regard to covers, by complying with the prescribed tightening torques;
• in regard to connectors
46
,
47
,
52
, through use of the available counterparts;
• in regard to the cable glands
48
,
49
,
51
, following the prescriptions indicated in this manual during installation.
The connectors to the battery pack are excluded from the assessment of the IP54 protection level (
39
,
35
,
38
), for which external
protection of a minimum of IP21 is required.
In regard to the connectors to the battery pack, the IP protection is provided by the battery pack box itself. Using the RECAT-BATT-
AP1 battery pack with the IP21 protection level, the protection level of the whole system becomes IP21.
4) Please refer to the document “String inverters – Product manual appendix” available at www.abb.com/solarinverters for information
on the quick-fit connector brand and model used in the inverter.
5) Optional