Procedure
1. Cut the DC power cables to make
sure that the length is sufficient for
connection at the DC busbars.
2. Strip the insulation from the end of
the cables. Make sure that the strip
length agrees with the cable lugs (A).
3. Attach the cable lugs to the end of the
wires.
4. Connect these wires on the DC busbar
connectors:
•
Outlet 1 DC+ wire, marked red, to
the connector X522 (B)
•
Outlet 1 DC- wire to the connector
X526 (C)
•
Outlet 2 DC+ wire, marked red, to the connector X523 (D)
•
Outlet 2 DC- wire to the connector X527 (E)
•
Outlet 3 DC+ wire, marked red, to the connector X524 (F)
•
Outlet 3 DC- wire to the connector X528 (G)
•
Outlet 4 DC+ wire, marked red, to the connector X525 (D)
•
Outlet 4 DC- wire to the connector X529 (E)
5. Install the nuts and washers (J) on the connectors.
6. Tighten the nuts to the correct torque. For the specification, refer to section
.
6.3.7
Connect the DC auxiliary power cables (24 V) to the power cabinet
Preliminary requirements
•
24 V DC auxiliary power
cables. Refer to section
•
Note:
•
The illustration shows the terminal blocks X4, X5, X6 and X7 on the
power cabinet and the connections treated in this section.
•
For the specific connections, refer to the installation brief, the
installation drawing and the installation manuals of the devices
installed in the system you ordered.
•
For information about the part numbers of the terminals, refer to
section
.
C
B
E
G
I
D
F
H
J A
Installation
HVC 200/300/360-EN | 002
47