Description
Setting for drives
Drive parameter
Selects the fieldbus A reference 1 type and scaling.
4
= Speed
50.04 FBA A ref1 type
Selects the actual value type and scaling according
to the currently active Ref1 mode defined in paramet-
er 50.04.
4
= Speed
50.07 FBA A act1 type
Displays the type of the fieldbus adapter module.
133
= PROFIsafe
1)
51.01 FBA A type
Selects the PROFINET IO protocol and the
PROFIdrive profile.
10
= PNIO Pdrive
51.02 Protocol/Profile
Ethernet communication rate is negotiated automat-
ically by the device.
0
= Auto
2)
51.03 Commrate
Configuration will be obtained from parameters
51.05…13 or from the PLC via the DCP protocol.
0
= Static IP
51.04 IP configuration
Sets the PROFIsafe destination address, that is, the
address of the FSPS-21 module in the safety com-
munication network.
This address must be the
same as is set in the F-
Parameters for the
PROFIsafe module proper-
ties (F_Dest_Add).
51.24 F Destination Ad-
dress
Status word
4
= SW 16bit
52.01 FBA DATA IN1
Actual value 1
5
= Act1 16bit
52.02 FBA DATA IN2
Output power
01.14
52.03 FBA data in3
DC voltage
01.11
52.05 FBA data in5
Control word
1
= CW 16bit
53.01 FBA DATA out1
Reference 1 (speed)
2
= Ref1 16bit
53.02 FBA DATA out2
Constant speed 1
22.26
53.03 FBA data out3
Constant speed 2
22.27
53.05 FBA data out5
Validates the configuration parameter settings.
1
= Refresh
51.27 FBA A par refresh
Selects speed control as the control mode 1 for ex-
ternal control location 1.
2
= Speed
19.12 Ext1 control mode
Selects the fieldbus A interface as the source of the
start and stop commands for external control location
1.
12
= Fieldbus A
20.01 Ext1 commands
Selects the fieldbus A reference 1 as the source for
speed reference 1.
4
= FB A REF1
22.11 Speed ref1 source
1) Read-only or automatically detected/set
2) Example
The start sequence for the parameter example above is given below.
Control word:
•
Reset the fieldbus communication fault (if active).
•
Enter 47Eh (1150 decimal) → READY TO SWITCH ON.
Enter 47Fh (1151 decimal) → OPERATING.
PROFINET IO – Start-up 59
Summary of Contents for FSPS-21
Page 1: ... OPTIONS FOR ABB DRIVES FSPS 21 safety functions fieldbus module User s manual ...
Page 2: ......
Page 4: ......
Page 11: ...Further information Table of contents 11 ...
Page 12: ...12 ...
Page 26: ...26 ...
Page 38: ...38 ...
Page 42: ...42 ...
Page 46: ...46 ...
Page 72: ...Switch or router ABB drive ABB drive ABB drive PLC Safety PLC 72 PROFINET IO Start up ...
Page 86: ...86 ...
Page 144: ...19 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 20 Insert values to blocks 144 PROFIsafe ...
Page 147: ...26 In device configuration right click FSPS icon and select Assign device name PROFIsafe 147 ...
Page 155: ...Select Addresses tab to see the correct IO addresses PROFIsafe 155 ...
Page 169: ...6 To check the Device number of the FSPS 21 module select the General tab PROFIsafe 169 ...
Page 178: ... starting the system does not cause any danger 178 Start up ...
Page 186: ...186 ...
Page 192: ...192 ...
Page 200: ...200 ...
Page 208: ...208 ...
Page 212: ......