F-Output data
Description
Name
Bit
Octet
Type
Reserved *)
0
Octet 1
Unsigned8 (used as
bits)
Reserved *)
1
Reserved *)
2
Reserved *)
3
Reserved *)
4
Reserved *)
5
Reserved *)
6
Reserved *)
7
Safe stop 1 monitoring
time limit (SS1-t) in 100
ms. Value range is
0...32767.
SS1-t_time
0 ... 15
2
Signed16
3
For example, value 21
= 2.1 s.
Negative values result
in 0.0 s.
*) The safety PLC shall set reserved bits to value 0. This ensures the compatibility with
future versions of the PROFIsafe profile where the reserved bits may be used.
■
FSPS-21 module modes and states
Power
down
(STO
active)
Start
up
(STO
active)
Running
Fail
safe
(STO
active)
Operational
Safe
(Module
passivation
&
reintegration)
Safe
(Module
passivation
with
a
command)
Safe
(Module
passivation)
Start
up
(STO
active)
A
B
RUN
Fault
detected
Description
Transition
Initial tests performed ok.
Start-up - Running
PROFIsafe 117
Summary of Contents for FSPS-21
Page 1: ... OPTIONS FOR ABB DRIVES FSPS 21 safety functions fieldbus module User s manual ...
Page 2: ......
Page 4: ......
Page 11: ...Further information Table of contents 11 ...
Page 12: ...12 ...
Page 26: ...26 ...
Page 38: ...38 ...
Page 42: ...42 ...
Page 46: ...46 ...
Page 72: ...Switch or router ABB drive ABB drive ABB drive PLC Safety PLC 72 PROFINET IO Start up ...
Page 86: ...86 ...
Page 144: ...19 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 20 Insert values to blocks 144 PROFIsafe ...
Page 147: ...26 In device configuration right click FSPS icon and select Assign device name PROFIsafe 147 ...
Page 155: ...Select Addresses tab to see the correct IO addresses PROFIsafe 155 ...
Page 169: ...6 To check the Device number of the FSPS 21 module select the General tab PROFIsafe 169 ...
Page 178: ... starting the system does not cause any danger 178 Start up ...
Page 186: ...186 ...
Page 192: ...192 ...
Page 200: ...200 ...
Page 208: ...208 ...
Page 212: ......