Preparing for installation
23
Planning your cabling
Select cabling according to your communication needs. Refer to the table below for recommended
cable gauge or type.
NOTICE
Table 2 gives a general description of the necessary cables. More detailed information is
found in Appendix B on page 89.
Always comply with national codes and electrical standards.
—
Table 2
Recommended cable gauge and type
Cable
Gauge/Type
Maximum length
power
Copper-only wire
(stranded WITh FErrULE or solid)
AWG #18 to AWG #12
90 °C 600V, UL and CSA type
15 m (50 ft) (AWG #12)
10 m (33 ft) (AWG #18)
Ground (earthing)
10 or 6 AWG
15 m (50 ft)
rS-485
24 AWG
1220 m (4003 ft)
Alarm relays
16 or 14 AWG
N/A
4–20 mA
18 AWG
N/A
SCADA (Ethernet)
Category 5 cable
100 m (328 ft)
OpTICAL (Ethernet)
ST-ST full duplex 62.5/125 multi-mode fiber
2000 m (6562 ft)
SErVICE (Ethernet)
Category 5 cable
3 m (10 ft)
USB (service port)
USB key only
N/A