Installing the sensor head
37
4
Connect the sensor head to the transformer valve.
An optional adapter can be used if the valve fitting is not NPT 1.5 (e.g., most North American valves
are NPT 2).
5
Tighten the connection with a wrench (50.8 mm [2-in] or adjustable wrench).
6
Once the head-valve connection is fully tightened, make sure that the sensor head is positioned
horizontally
and that its sampling access panel is pointing upwards. Rotate the head as necessary.
NOTICE
Failure to position the CoreSense M10 sensor head horizontally, with the access panel
pointing upwards, will cause the thermal pump to malfunction and may result in
erroneous readings.