Configuring CoreSense M10
69
Activating the thermal pump
NOTICE
The thermal pump is designed to operate while immersed in transformer oil. It will fail
within minutes
if operated in air.
For configuration purposes, the sensor head can be powered when it does not contain any oil. However,
the thermal pump must be turned OFF
.
The CoreSense M10 sensor head is delivered with the thermal pump turned OFF. When installation is
complete and the sensor head is in contact with oil, make sure to activate the thermal pump.
To activate the thermal pump:
1
From the CoreSense M10 dashboard (see Figure 47), click
Settings
. The Settings page appears (see
2
Click
Administration settings
and enter your password (for more information on setting passwords,
3
Scroll down to the
Application settings
section and check the
Enable thermal pump
box.
4
At the bottom of the page, click
Apply
to confirm activation of the thermal pump.
—
Figure 54
Enabling the thermal pump