Modifications reserved
Page 8/25
3
Input characteristics
Conceptpower DPA 500
UPS frame
UPS module
Unit
Power, rated
500
100
kW
Voltage (steady-state, r.m.s), rated:
3x380/220V+N
3x400/230V+N
3x415/240V+N
VAC
Tolerance, referred to 400/230V
-10 / +15 at <100% load
-20 / +15 at <80% load,
-30 / +15 at <60% load
%
Frequency, rated
50
Hz
Tolerance, referred to 50Hz
-30 / +40
%
Current (r.m.s), rated
(with battery charged and input 400/230V)
760
152
A
Current (r.m.s), maximum
(with charging batt. and input 400/230V)
835
167
A
Total harmonic distortion (THDi)
≤ 3.5
%
In-rush current
< 100% of the rated current
A or %
Power factor
0.99 @ 100% load
Rated short-time withstand current (I
CW
)
25 for 1s
-
kA, s
AC power distribution system: TN-S, TN-C, TN-C-S, TT
note: in static bypass mode or eco-mode TN-C and TN-C-S can cause PE current to rise above 5% of phase currents.
Phases required
3
Neutral required
yes
ADDITIONAL AND USUAL INFORMATION
Connection:
5 wires, 3 phase + N + PE
Cable entry:
Top or bottom
Accessibility:
Frontal
Walk In/Soft Start:
Yes
Back feed protection:
Yes
Summary of Contents for Conceptpower DPA 500
Page 1: ... Copyright 2017 ABB All rights reserved Operating manual Conceptpower DPA 500 100 500 kW ...
Page 2: ......
Page 79: ... Copyright 2017 ABB All rights reserved Appendix A Xtra VFI 3 ph UPS products ...
Page 88: ...Modifications reserved Page 88 94 Attachments Technical data sheet ...
Page 90: ......
Page 91: ... Copyright 2017 ABB All rights reserved Technical data sheet Conceptpower DPA 500 100 500 kW ...