When the UPS is operating in
Eco mode
, the efficiency of the system is higher (99%). In the event of a
mains failure the load will automatically be transferred from mains to inverter within 5 ms (this is valid
for single and parallel systems). The battery charger remains active in
Eco mode
.
Operating in
Eco mode
is recommended only if the load can tolerate interruptions of 3-5 ms (transfer
time from
Eco mode
to
Online mode
).
NOTE
TO HAVE THE MOST ESSENTIAL SECURITY LEVEL, WE RECOMMEND TO
RUN THE UPS ON ONLINE OPERATION MODE
6.4.8.4
Maintenance bypass mode
Before transferring the load to maintenance bypass (IA1) always check that all the UPS-modules
are in Eco-Mode (Bypass-Mode).
The
Maintenance Bypass mode
is performed using the IA1 bypass switch in the front of the UPS:
Switch
Position
Effect
Status
ON
Maintenance bypass switch closed:
(Load supplied directly from mains)
Warning symbol indicates in the display:
“Manual bypass is closed”
OFF
Maintenance bypass switch open:
Normal operating condition (Load
supplied by inverter)
Warning symbol indicates in the display:
“Manual bypass is opened”
NOTE
ON MANUAL OR MAINTANENCE BYPASS MODE, THE LOAD IS NOT
PROTECTED AGAINST ANY MAINS FAILURES OR MAINS DISTURBANCES
Summary of Contents for Conceptpower DPA 500
Page 1: ... Copyright 2017 ABB All rights reserved Operating manual Conceptpower DPA 500 100 500 kW ...
Page 2: ......
Page 79: ... Copyright 2017 ABB All rights reserved Appendix A Xtra VFI 3 ph UPS products ...
Page 88: ...Modifications reserved Page 88 94 Attachments Technical data sheet ...
Page 90: ......
Page 91: ... Copyright 2017 ABB All rights reserved Technical data sheet Conceptpower DPA 500 100 500 kW ...