Table 4: Recommended AC wiring (copper wires) according to IEC 60950-1, recommended
fuse ratings for slow line fuses (gL) or circuit breakers (CB), connection terminal size and max.
tightening torque.
Rated
power
(kW)
Rectifier input
Max. rectifier input current
with battery charging
835A at 230V / 875A at 220V
Bypass input
Max. bypass input current
732A at 230V / 765A at 220V
Output
Rated output current in normal
conditions
725A at 230V / 758A at 220V
Fuse B
Type: gL or CB
(quantity x A)
Cable B
(quantity x
mm
2
)
Fuse C
Type: gL or CB
(quantity x A)
Cable B
(quantity x
mm
2
)
Fuse D
Type: gL or CB
(only needed in
parallel system)
(quantity x mm
2
)
Cable D
(quantity x mm
2
)
500
3 x 1000A
(3 pole, bolded N)
5x(2x240)
5x(3x120)
3 x 800A
(3 pole, bolded N)
5x(2x240)
5x(3x120)
4 x 800A
(4 pole)
5x(2x240)
5x(3x120)
All connection points are bus-bar, M12. Recommended tightening torque 42 Nm
Table 5: Recommended DC wiring (copper wires) according to IEC 60950-1, recommended
fuse ratings for fast acting fuses (gR) or circuit breakers (CB), connection terminal size and max.
tightening torque.
Common battery
Rated power
(kW)
Fuse E
Type: gR or CB
(quantity x A)
Cable E
(quantity x mm
2
)
500
2x1250A
(2 pole)
2x(3x240)
2x(4x150)
All connection points are bus-bar, M12. Recommended tightening torque 42 Nm
Summary of Contents for Conceptpower DPA 500
Page 1: ... Copyright 2017 ABB All rights reserved Operating manual Conceptpower DPA 500 100 500 kW ...
Page 2: ......
Page 79: ... Copyright 2017 ABB All rights reserved Appendix A Xtra VFI 3 ph UPS products ...
Page 88: ...Modifications reserved Page 88 94 Attachments Technical data sheet ...
Page 90: ......
Page 91: ... Copyright 2017 ABB All rights reserved Technical data sheet Conceptpower DPA 500 100 500 kW ...