Modifications reserved
Page 39/94
Mains on X1
JP2
JP3
JP4
480V
OFF
OFF
OFF
230V
ON
ON
OFF
120V
ON
ON
ON
6.2.4
Multidrop Configuration
Multidrop cable connection
Insert the splitter/s supplied with the installation inside the Multidrop connector/s
JR2 on NW22085 on all middle unit/s.
Connect the “Previous” end of the multidrop cable on the First Unit and the
“Next” end on the second Unit (If more than two unit inside the splitter).
Proceed on the same way with all other unit on the installation as shown on the
picture.
Board NW22085 Jumper & Switches configuration
Verify that the customer interface board (
NW22085)
of each unit correctly configured according to the
following table
JUMPER JP 2
on PCB NW22085
D
(with ROM76-12) or
NW22085
E
or later versions
First unit
OFF
Middle Unit
ON
Last Unit
ON
Note: on the (older) versions NW22085B/C without ROM76-12 make a bridge between X3-11 & X3-12.
6.2.5
ON/OFF – Main Buttons
The ON/OFF-Buttons serve to shutdown the UPS-system for service or maintenance or for
emergency reasons.
NOTE
WHEN BOTH ON/OFF BUTTONS ON ALL UPS MODULES IN A PARALLEL
SYSTEM ARE PUSHED THE POWER SUPPLY TO THE LOAD WILL BE
INTERRUPTED
Prev
Next
Prev
Next
First Unit
Middle Unit
Last Unit
Summary of Contents for Conceptpower DPA 500
Page 1: ... Copyright 2017 ABB All rights reserved Operating manual Conceptpower DPA 500 100 500 kW ...
Page 2: ......
Page 79: ... Copyright 2017 ABB All rights reserved Appendix A Xtra VFI 3 ph UPS products ...
Page 88: ...Modifications reserved Page 88 94 Attachments Technical data sheet ...
Page 90: ......
Page 91: ... Copyright 2017 ABB All rights reserved Technical data sheet Conceptpower DPA 500 100 500 kW ...