Table 2: Recommended AC wiring (copper wires) according to IEC 60950-1, recommended
fuse ratings for slow line fuses (gL) or circuit breakers (CB), connection terminal size and max.
tightening torque.
Rated
power
(kW)
Single input
Max. rectifier input current with charging batt.
835A at 230V / 875A at 220V
Output
Rated output current in normal conditions
725A at 230V / 758A at 220V
Fuse A
Type: gL or CB
(quantity x A)
Cable A
(quantity x mm
2
)
Fuse D
Type: gL or CB
(only needed in parallel
system)
(quantity x mm
2
)
Cable D
(quantity x mm
2
)
500
3 x 1000A
(3 pole, bolded N)
5x(2x240)
5x(3x120)
4 x 800A
(4 pole)
5x(2x240)
5x(3x120)
All connection points are bus-bar, M12. Recommended tightening torque 42 Nm
Table 3: Recommended DC wiring (copper wires) according to IEC 60950-1, recommended
fuse ratings for fast acting fuses (gR) or circuit breakers (CB), connection terminal size and max.
tightening torque.
Separate batteries
Rated power
(kW)
Fuse E
Type: gR or CB
(quantity x A)
Cable E
(quantity x mm
2
)
100
(one module)
2 x 250A
(2 pole)
2x(1x120) with 40-45 12V battery blocks
2x(1x95) with 46-50 12V battery blocks
All connection points are bus-bar, M8. Recommended tightening torque 24 Nm
Summary of Contents for Conceptpower DPA 500
Page 1: ... Copyright 2017 ABB All rights reserved Operating manual Conceptpower DPA 500 100 500 kW ...
Page 2: ......
Page 79: ... Copyright 2017 ABB All rights reserved Appendix A Xtra VFI 3 ph UPS products ...
Page 88: ...Modifications reserved Page 88 94 Attachments Technical data sheet ...
Page 90: ......
Page 91: ... Copyright 2017 ABB All rights reserved Technical data sheet Conceptpower DPA 500 100 500 kW ...