Wiring with the display system
232
1SVC 440 795 M1100
Operating modes
• Q: Acts on the outputs Q.., *Q.., S.., *S.., *SN.., QA01; *:
Station address
• M: Acts on the marker range MD01 to MD48.
• ALL: Acts on Q and M.
Contacts
MR01Q1 to MR32Q1
The contact switches on the marker if the trigger coil MR…T
has the state 1.
Coils
MR01T to MR32T: Trigger coils
Memory requirement of the data function block
The master reset function block requires 20 bytes of memory.
Function of the data master reset
The outputs or the markers are set to the state 0 in
accordance with the operating mode when a rising edge is
detected on the trigger coil.
The contacts MR01Q1 to MR32Q1 assume the state of their
own trigger coil.
Numerical converter
The display system provides 32 numerical converters NC01
to NC32.
A numerical converter function block enables you to convert
BCD coded values to decimal values or decimal coded values
to BCD coded values.
Wiring of a numerical converter
A numerical converter in the circuit diagram only has the
enable coil.
Figure: 123:
Display system circuit diagram with numerical converter
h
The master reset function block should be used as the last
function block in a program so that all data ranges are
cleared reliably. Otherwise subsequent function blocks
may overwrite the data ranges.
I 05---------------------------Ä NC02EN