Wiring with the display system
206
1SVC 440 795 M1100
Parameter display and parameter set for PID
controller:
In the parameter display of a PID controller you set the operating
mode, the setpoints and enable the parameter display.
Operating modes of the PID controller
Z
Inputs
The function block inputs
>I1, >I2, >KP, >TN,
>TV, >TC
and
>MV
can have the following operands:
• Constants
• Markers MD, MW, MB
• Analog inputs IA01 to IA04
– IA01: Terminal I7
– IA02: Terminal I8
– IA03: Terminal I11
– IA04: Terminal I12
• Analog output QA01
• Actual value …QV> of another function block
DC02 UNP
+
>I1
>I2
>KP
>TN
>TV
>TC
>MV
QV>
DC02
PID controller function block number 02
UNP
Unipolar mode
+
Appears in the parameter display
>I1
Setpoint of PID controller
>I2
Actual value of PID controller
>KP
Proportional gain K
p
>TN
Reset time T
n
>TV
Rate time T
v
>TC
Scan time
>MV
Manual manipulated variable
QV>
Manipulated variable
Parameter
Manipulated variable is output as
UNP
Unipolar 12-bit value 0 to +4095
BIP
Bipolar 13-bit value (signed 12-bit value) –4096 to +4095