Wiring with the display system
176
1SVC 440 795 M1100
Example:
Comparison of marker blocks, range overlap error.
12 bytes are to be copied starting from MW60. MW64 is
specified as destination address.
Parameters of BT01 function block:
Comparison range 1:
>I1 MW60
Comparison range 2:
>I2 MW64
Number of bytes:
>NO 12
The error message “Both ranges overlap” is output.
BC01E2 is 1.
Example: Copying of marker bytes, invalid offset error.
The value of marker word MW40 is to be copied to MW54
and subsequent marker words. The block length is specified
by the value of the counter C 01QV.
Parameters of BT01 function block:
Comparison range 1:
>I1 MW40
Comparison range 2:
>I2 MW54
Number of bytes:
>NO C 01QV
The message “The specified offset of the destination range
is outside of the permissible range” is output.
BT01E3 is 1.
h
The copy operation is in byte format. MW60 to MW64 is
8 bytes. The number of bytes is 12 bytes.
h
The value of C 01QV is 10 042. This value is too big. The
value at
>NO
can be between 1 and +383.